3P4W POWER ANALYZER
|
Model No.︰ | TES-3600 |
Brand Name︰ | TES |
Country of Origin︰ | Taiwan, China |
Minimum Order︰ | 1 pc |
|
|
|
|
|
|
|
- 10 Display Easy - to - View LCD Screen.
- Connectors for 4 Current Sensing Clamps.
- 1P2W, 1P3W, 3P3W2M & 3P4W Power Measurement.
- True RMS Sensing.
- Power KW, KVAR, KVA, PF, θ ,Hz, & Energy KWh, KVARh & KVAh Measurement.
- Phase sequency indicator function.
- Backlight display function.
- Manual Data Memory and Read (99 sets).
- Data Logging (512KB Memory, 20,000 sets)
- Programmable Trigger - Points and Start / Stop Time.
- RS-232 Optical Interface with three phase voltage / current Waveform display and Harmonic analysis.
- Easy - to - use Push - Button Operation.
- Light Weight, Portable Design.
|
|
|
Ranges
|
Method
|
Accuracy
|
Input impedance
|
600.0V
|
True RMS
|
± 0.5%rdg ± 10dgts (>30V)
|
2M Ω
|
|
Ranges
|
Method
|
Accuracy
|
250A 、 500A 、 1000A
|
True RMS
|
± 0.5%rdg ± 10dgts + clamp on sensor specifications
|
|
Active Power Measurement (KW) |
Ranges
|
Accuracy
|
Effect of power factor
|
600.0KW
|
± 0.5%rdg ± 10dgts + clamp on sensor specifications
|
± 0.1%rdg
|
|
Reactive Power Measurement (KVAR) |
Ranges
|
Accuracy
|
Effect of power factor
|
600.0KVAR
|
± 0.5%rdg ± 10dgts + clamp on sensor specifications
|
± 0.1%rdg
|
|
Apparent Power Measurement (KVA) |
Ranges
|
Accuracy
|
600.0KVA
|
± 0.5%rdg ± 10dgts + clamp on sensor specifications
|
|
Power Integration Measurement |
Power Integration
|
Resolution
|
Accuracy
|
0.0KWh to 9999MWh
|
0.1KWh
|
± 0.5%rdg ± 10dgts + clamp on sensor specifications
|
0.0Kvarh to 9999Mvarh
|
0.1Kvarh
|
0.0KVAh to 9999MVAh
|
0.1KVAh
|
|
Ranges
|
Accuracy
|
Polarity display
|
-1.000(lead) to 0.000 to + 1.000 (lag)
|
± 1dgt for each calculation from measured values
|
When the current lags the voltage unsigned ; when the current leads the voltage : "-".
|
|
Ranges
|
Measurement source
|
Accuracy
|
40Hz to 100Hz
|
Voltage U1
|
± 0.5%rdg ± 1dgt
|
|
Size |
235(L)x116(W)x54(H)mm (9.3"Lx4.6"Wx2.1"H) |
Operating Temperature and Humidity |
0 ℃ to 50 ℃ (32 ℉ to 122 ℉ ) R.H. < 80% non-condensing |
Storage Temperature and Humidity |
- 10 ℃ to 60 ℃ (14 ℉ to 140 ℉ ) R.H. < 70% non-condensing |
Accessories |
1) Instruction manual
2) Software CD Rom / Optical RS-232 interface
3) Deluxe carrying case
4) Battery (“AA” 1.5V x 8pcs )
5) AC adaptor (110V -> 12V ; 220V -> 12V)
6) 4pcs current clamp transducer (1, 2, 3, 4 cable length 3 meters) (1000A AC, jaw opening 40mm)
7) 4pcs crocodiles test leads (blue, yellow, red, black, wire length 3 meters)
|
|
|
|
|
|
Product Image
|
|